Software Setup 5-3
Data Exchange with the Modbus Plus Expansion Board
This section describes the register interface used for data exchange
with the Series H control. Motor drive parameters are mapped to
Modbus Plus Data/Holding registers (4xxxx). Parameters can be read
from or written to the Series H control by reading from or writing to the
appropriate Modbus Plus registers.
Common Area Register Mapping (All Series H Controls)
Register
Address
T# Read/Write Description
40001 Read/Write Watchdog polling flag (see Note 4)
41000 0 Write Only Null Transaction (see Note 3)
41001
43999
61 Read/Write Baldor Control Parameters 10013999
(see Baldor Drive Installation & Operating Manual)
44000
46999
Reserved for additions.
49012 41 Read/Write Watchdog Time (0=disable) (10 ms minimum for
vector) (1 sec. minimum for inverter) (see Note 3)